XTS8610 Series
Advanced Sync Pro IEC61850-3 Industrial NTP/PTP Server Grandmaster Clock

XTS8610 Series

Advanced Sync Pro IEC61850-3 Industrial NTP/PTP Server Grandmaster Clock

Key Features:

  • IEC 61850-3 HV & IEEE 1613 Certified NTP Server & IEEE 1588 PTP Grandmaster
  • -40 to +85 °C Operating Temperature, IP30 Protection, and Up to 5100 m Altitude
  • MIL-STD-810F Certified for Environmental and Transportation Reliability
  • Dual Hot Swappable Power Modules with Wide Input Range
  • Full Redundancy Across Power, System, Network, and Link Layers
  • <40 ns PRTC-B/PTP, <50 µs NTP Accuracy, Calnex Verified
  • Excellent Holdover Performance: <0.5 μs/8 Hours / <72 μs/7 Days
  • Supports Power, Telecom, AVBTSN and Enterprise Profile
  • Four Ethernet Ports: Two PTP-Capable Combo Ports, All Four NTP-Capable
  • Dual Media Combo Ports Enable Cost-Effective Copper/Fiber Deployment
  • Supports Multi-Constellation GNSS with Anti-Jamming and Anti-Spoofing
  • Optional Multi-band GNSS model supporting up to concurrent constellations
  • Antenna Fault Detection and Protection: Short Circuit and Disconnection
  • Configurable IRIG-B (TTL, AM, RS-485), PPS, and 10 MHz Outputs
  • Built in 40X2 LCM for display and configuration
  • Streamlined cable Management with Rear-Facing connections
  • Standard 5-Year Warranty, Upgradeable to 10 Years.

Description

Technical Specification

Model Name NTS8610 Series

GNSS Receiver Specifications

GNSS Input ports 1x GNSS Input; SMA (F) – active Antenna
GNSS Module specific Information Multi-Constellation Supported: GPS L1, GLONASS L1, BeiDou B1, Galileo E1 Maximum Concurrent Constellations: 3

 

Leap Second: Supported Sensitivity for GPS:

•  Tracking: -166 dBm

•  Reacquisition: -160 dBm

•  Cold Start: -148 dBm

•         Hot Start: -160 dBm

Acquisition Times Cold Start: < 45 seconds

Warm Start: < 7 seconds

Antenna Requirements 3.3 V, < 50 mA

Minimum gain=5dB; Maximum gain + Cable Attenuation ≤ 40dB

GNSS Vulnerability Mitigation Jamming: Support Detection, Warning and Switch to OCXO Holdover

Spoofing: Support Detection, Warning and Switch to OCXO Holdover (GNSS Antenna Only)

Antenna Vulnerability Mitigation Antenna Cable Short: Support Detection, Warning and Switch to OCXO Holdover

Antenna Disconnection: Support Detection, Warning and Switch to OCXO Holdover

Multiple Bands GNSS Receiver Specifications

GNSS Input ports 1x GNSS Input; TNC (F) – active Antenna
GNSS Module specific Information Multi-Constellation Supported:

GPS: L1C/A, L2C or L5

Galileo: E1, E5a or E5b

BeiDou: B1I, B2I or B2a

GLONASS: L1OF

NavIC: L5

Maximum Concurrent Constellation: 4

Leap Second: Supported

Sensitivity for GPS + GLONASS + Galieo + BeiDou

• Tracking: -167 dBm

• Reacquisition: -160 dBm

• Cold Start: -148 dBm

• Hot Start: -157 dBm

Acquisition Times Cold Start: < 24 seconds

Warm Start: < 2 seconds

Antenna Requirements 3.3 V, < 50 mA

Minimum gain=6dB; Maximum gain + Cable Attenuation ≤ 30dB

GNSS Vulnerability Mitigation Jamming: Support Detection, Warning and Switch to OCXO Holdover

Spoofing: Support Detection, Warning and Switch to OCXO Holdover (GNSS Antenna Only)

Antenna Vulnerability Mitigation Antenna Cable Short: Support Detection, Warning and Switch to OCXO Holdover

Antenna Disconnection: Support Detection, Warning and Switch to OCXO Holdover

 

 

Antenna Specifications (Accessories)

GNSS Antenna GNSS receiver: GPS L1, GLONASS L1, BeiDou B1, Galileo E1 LNA Gain: 40dB min

Weather-Proof Housing: IP69K

Operating and Storage Temperature: -40°C ~85°C

ESD: ±15KV Air Discharge

Mechanical size: 66.5 mm dia. x 21 mm H

MIL-STD-810F

Supply Voltage Range: 2.5 to 16VDC

GPS Antenna GNSS receiver: GPS L1, Galileo

Weather-Proof Housing: IP69K

Operating and Storage Temperature: -40°C ~85°C

ESD: ±15KV Air Discharge

Mechanical size: 66.5 mm dia. x 21 mm H

MIL-STD-810F

Supply Voltage Range: 2.5 to 16VDC

Anti Jamming GNSS Antenna GNSS receiver: GPS L1, GLONASS L1, BeiDou B1, Galileo E1 LNA Gain: 40dB Typ.

Weather-Proof Housing: IP69K

Operating and Storage Temperature: -40°C ~85°C

ESD: ±15KV Air Discharge

Mechanical size: 66.5 mm dia. x 21 mm H

MIL-STD-810F

Supply Voltage Range: 2.5 to 16VDC

Multi-Bands GNSS Antenna (XTS8610) GNSS Receiver:

GPS: L1C/A, L2C or L5

Galileo: E1, E5a or E5b

BeiDou: B1I, B2I or B2a

GLONASS: L1OF

NavIC: L5

LNA Gain: 37dB min

Weather-Proof Housing: IP69K

Operating and Storage Temperature: -40°C – 85°C

ESD: ±15KV Air Discharge

Mechanical Size: 66.5 mm dia. x 21 mm H

MIL-STD-810F

Supply Voltage Range: 2.5 to 16VDC

Max. Antenna Cable Length Antenna cable:

Without amplifier:

LMR-400: 150M CFD-200: 50M RG58A/U: 25M

With Amplifier:

LMR-400: 250M CFD-200: 80M RG58A/U: 50M

Max. Sync-out Cable Length RG58 A/U Sync-Out cable:

1PPS, 10MHz, IRIG-B TTL: 150M

IRIG-B AM: 150M @1K impedance, 300M @10K impedance IRIG-B RS485: 1200M

Proven Clock Accuracy (Relative to UTC)

1PPS ±40 ns Peak *1
Demodulated IRIG-B ±40 ns Peak *1
Modulated IRIG-B AM ±1 μs Peak *1
RS-485 IRIG-B ±100 ns Peak *1
PTP Timestamp ±40 ns Peak *1
NTP Timestamp ±50 us Peak , ±40 us Average *1
Holdover accuracy – OCXO < 0.5 us / 8 hours / < 72 us / 7 days *2
  *1. Device locked to satellites for at least 24 hours.

*2. Device locked to satellites for at least 48 hours before holdover

Network Interface

Ethernet Standards IEEE 802.3 10BaseT

IEEE 802.3u 100BaseT(X)

IEEE 802.3ab for 1000BaseT(X) IEEE 802.3u for 100Base-FX IEEE 802.3z for 1000Base-X

Gigabit Ethernet Ports Two Combo ports, 2x 10/100/1000BASE-T(X) RJ45 or 2x 100/1000 Base-X SFP Support Synchronous Ethernet (SyncE) per ITU-T G.8261 ITU-T, G.8262 and G.8264 ESMC), PTP-Capable and NTP-Capable
Fast Ethernet Ports 2x 10/100 BASE-T(X) RJ45, NTP-Capable

LCD Display and Control Buttons

LCD Spec Character Display LCD 40×2

5×8 Dots Includes Cursor

LCD Operating Temperature Range: -20°C to 70°C

LCD Over-Temperature Protection

Control Buttons Up, Down, Left, Right, Menu, Enter, Back

 

I/O

Console 1x DB9 Serial Console Port
SD Slot 1x micro-SD slot
Relay-Alarm Contact Three Pins Relay with NC, NO and GND.

Rated Operational Voltage: 24-250 VDC

Continuous carrier: 3 A max. 75VA max

Dropout Time: ≤ 6 ms typical

Pickup time: ≤ 8 ms

Sync Module S2

Sync1 ~ Sync2 Two configurable output channels (coaxial BNC (F) connector):

1. 1PPS/PPM/PPH Output (Square Wave, configurable pulse width)

2. IRIG-B TTL Output (Support IEEE 1344 and C37.118.1)

3. AFNOR French Time Code Output

4. ASCII Timestamp Output*

Sync3 ~ Sync5 Three configurable output channels (Sync 3 – Sync 5, coaxial BNC (F) connector):

1. 1PPS/PPM/PPH Output (Square Wave, configurable pulse width

2. IRIG-B TTL B000~B007 Output (Support IEEE 1344 and C37.118.1)

3. IRIG-B AM B120~B127 Output (Support IEEE 1344 and C37.118.1)

4. AFNOR French Time Code

5. ASCII Timestamp Output*

Sync6 One configurable output channel (Sync 6, TB3 connector):

1. IRIG-B RS-485 B000~B007 Output (Support IEEE 1344 and C37.118.1)

2. AFNOR French Time Code Output

Sync Module S3

Sync1 ~ Sync2 Two configurable output channels (coaxial BNC (F) connector):

1. 1PPS/PPM/PPH Output (Square Wave, configurable pulse width)

2. IRIG-B TTL Output (Support IEEE 1344 and C37.118.1)

3. AFNOR French Time Code Output

4. ASCII Timestamp Output*

Sync3 One configurable output channel (Sync 3, coaxial BNC (F) connector):

1. 1PPS/PPM/PPH Output (Square Wave, configurable pulse width)

2. IRIG-B TTL B000~B007 Output (Support IEEE 1344 and C37.118.1)

3. IRIG-B AM B120~B127 Output (Support IEEE 1344 and C37.118.1)

4. AFNOR French Time Code

5. ASCII Timestamp Output*

Sync4 One configurable input channel (coaxial BNC (F) connector):

1. IRIG-B TTL B000~B007 Input (Support IEEE 1344 and C37.118.1)

2. 1PPS input

3. AFNOR French Time Code TTL Input

Sync5 One configurable modulated input channel (coaxial BNC (F) connector):

1. IRIG-B AM B120~B127 Input (Support IEEE 1344 and C37.118.1)

2. Modulated AFNOR French Time Code Input

Sync6 One configurable input/output channel (Sync 6, TB3 connector):

1. IRIG-B RS-485 B000~B007 Input (Support IEEE 1344 and C37.118.1)

2. IRIG-B RS-485 B000~B007 Output (Support IEEE 1344 and C37.118.1)

3. AFNOR French Time Code RS-485 Input

4. AFNOR French Time Code RS-485 Output

Sync7 One configurable output channel (ST (F) connector):

1. 1PPS/PPM/PPH Output (Square Wave, configurable pulse width)

2. IRIG-B TTL Output (Support IEEE 1344 and C37.118.1)

3. AFNOR French Time Code Output

4. ASCII Timestamp Output*

 

Electrical output Drive Levels

1PPS/IRIG-B TTL Output 5VDC 125 mA TTL compliant
Modulated IRIG-B Output 5Vp-p, 3.3:1 ratio, AM, Sinewave
1PPS/IRIG-B TTL Input 5VDC HCMOS, > 2.0V High <0.8V Low
Modulated IRIG-B Input 1Vp-p to 8 Vp-p, ratio 3.3:1, AM
IRIG-B Fiber TTL 820nm, Different fiber size: 50/125um, 62.5/125um, Output Driver Typ. 13.1uW
IRIG-B RS485 Input/Output ±5 VDC IRIG-B Half-Duplex; 32 Transceivers Max. a bus

 

Frequency

Oscillator Advanced managed OCXO, with temperature drifting compensation

IEEE1588 Profiles

Default IEEE 1588V2 (PTPv2)

Default UDP (IEEE1588-2008 Annex D and J)

Default 802.3 (IEEE1588-2008 Annex F and J)

Power IEC/IEEE61850-9-3-2016 Power Utility Profile

IEEE C37.238-2011 Power Profile, with VLAN support

IEEE C37.238-2017 Power Profile, with VLAN support

Telecom ITUT-G.8265.1 Frequency

ITUT-G.8275.1 Phase/Time

ITUT-G.8275.2 Phase/Time

AVBTSN 802.1AS Profile
Enterprise Enterprise profile
*Media Broadcast

(In Development Plan)

SMPTE ST 2059-2

AES67 Media Profile

System Moods

GNSS Locked Mood Synchronizes time with GNSS signals for high accuracy
Handover Mood Maintains time using the OCXO clock after GNSS is unavailable
Free Run Mood Operates independently using RTC as the time source along with the OCXO clock

 

Functions

Network Synchronization RFC 1119 (NTPv2) Server

RFC 1305 (NTPv3) Server

RFC 5905 (NTPv4) Server

RFC 1769 (SNTPv3) Server

RFC 2030 (SNTPv4) Server

Network Protocols VLAN (IEEE 802.1q) filtering/tagging

IEEE 802.1p QoS

DSCP IPv4, IPv6 TCP, UDP

DHCP Client TACAS+/ RADIUS

Redundancy Devices Clustering (NTP Only)

PRP (IEC 62439-3)

Bonding – Active & Backup Bonding — LACP

Combo Ports

Management HTTP, HTTPS

SNMP v1/v2,v3

SSH/ Telnet (CLI), could be enabled/disabled Console CLI

Estimated Time Accuracy GNSS Status

Power Status PTP & NTP Status

SD/MMC Backup & Restore

Events & Alarms Event

Log

Syslog

Relay & Alarm Management

SNMP Trap

Physical Characteristics

Housing

Dimension (W x H x D)

Weight

Installation

SPCC w/Zinc Plated Body + Aluminum cover IP40 Metal Housing

440 x 300 x 44

Chassis made of 1 mm SECC Sheet

 

3.9KG Max

1U Rack-mountable

Power Supply Modules

DC Module Rated Supply Voltage: ±24 – ±60 VDC

Input Voltage Range: ±20 – ±66 VDC

AC Module Rated Supply Voltage:

110 – 240 VAC, 50/60 HZ

110 – 250 VDC

Input Voltage Range:

85 – 264 VAC, 50/60 HZ

88 – 300 VDC

Power Consumption Approximately 15 W (Typical)

Approximately 20 W (Max)

Environmental Limits

Operating Temperature

Storage Temperature

Operating Altitude

Ambient Relative Humidity

-40°C to +85°C (-40°F to 185°F)

-40°C to +85°C (-40°F to 185°F)

5100m

5% to 95% (Non-condensing)

Regularity Approvals

   Safety LVD EN 62368-1 (Certified Operating Temperature: 75°C), IEC 60255-5

 

   EMC

FCC(EMI): FCC Part 15, Subpart B, Class A CE(EMI): EN 55032, EN 61000-6-4, Class A

EN 61000-3-2 (Current Harmonics) EN 61000-3-3 (Voltage Flicker) CE(EMS): EN 55035,

EN 61000-6-2

CE(GNSS): EN 303 413. EN 301 489-19

IEC 60255-25, IEC 60255-22-1

 

 

 

   Power Automation IEC61850-3, IEEE 1613
Test Item Value Level
   IEC 61000-4-2 ESD Contact Discharge Air Discharge ±8KV

±15KV

4

4

   IEC 61000-4-3 RS Enclosure Port 10(V/m), 80-3000MHz

20(V/m), 80-1000MHz

3
 

   IEC 61000-4-4

 

EFT

AC Power Port DC Power Port Signal Port ±4.0KV

±4.0KV

±2.0KV

4

4

Special

 

 

   IEC 61000-4-5

 

 

Surge

AC Power Port AC Power Port DC Power Port DC Power Port Signal Port  

Line-to Line±2.0kV Line-to Earth±4.0kV Line-to Line±1.0kV Line-to Earth±2.0kV Line-to Earth±4.0kV

4

4

4

3

4

   IEC 61000-4-6 CS 0.15-80MHz 10V rms 0.15-80MHz, 80% AM 3
   IEC 61000-4-8 PFMF (Enclosure) 100A/m continuous, 1000A/m (3s) 5
 

 

   IEC 61000-4-11

 

 

DIP

 

 

AC Power Port

30% reduction (Voltage Dips), 1 period

60% reduction (Voltage Dips), 50 period 100%, reduction (Voltage interruptions), 5 period

100% reduction (Voltage interruptions), 50 period

 

 

 

 

   IEC 61000-4-16

Main Frequency Voltage DC Input Port Signal Port 30V Continuous, 300V 1s 30V Continuous, 300V 1s 4

4

   IEC 61000-4-17 Ripple DC Input Port 10% of unit 3
 

   IEC 61000-4-18

 

Damped Oscillatory

 

AC Power Port

2.5KV common,

1KV differential mode @ 1MHz

 

3

    Signal Port Telecommunication Port 2.5KV common,

1KV differential mode @ 1MHz

 

3

 

   IEC 61000-4-29

 

DC Voltage Dips & Interruptions

 

DC Input Port

30% Reduction (Voltage Dips):0.1 sec 60% Reduction (Voltage Dips):0.1 sec 100% Reduction

(Voltage Interruption):0.05 sec

   IEC 60255-22-1 1 MHz burst

immunity

AC Power Port

AC Power Port

DC Power Port

DC Power Port

Signal Port

Line-to Line±1.0 kV

Line-to Earth±2.5 kV

Line-to Line±1.0 kV

Line-to Earth±2.5 kV

Line-to Earth±1.0 kV

Shock Drop Vibration MIL-STD-810G Method 516.5

MIL-STD-810F Method 516.5

MIL-STD-810F Method 514.5 C-1 & C-2

RoHS2 Yes
MTBF 20 years
Warranty 5 years / Upgradable to 10 years
Physical Characteristics

Housing
Dimension (W x H x D) WeightInstalleation Power inputs
SPCC IP30 Metal Housing

223 x 251 x44 mm (not including screws and rack-mount kit) TBD

1U Rack-mountable

24-60 VDC(Dual Input) or 110-240VAC/12–240VDC

Environmental Limits
Operating Temperature Storage Temperature Ambient Relative Humidity -40°C to +70°C (-40°F to 185°F) / LCM display maximum 0 to +70 °C

-40°C to +75°C (-40°F to 185°F) / LCM display maximum -30 to +80 °C 5% to 95% (Non-condensing)

REGULATORY APPROVALS
Regulatory Approvals
Safety EN/IEC 62368
 

EMC

FCC Part 15, Subpart B, Class A, EN 55032, EN 61000-6-4:Class A, EN 61000-3-2, EN 61000-3-3
Power Automation IEC61850-3, IEEE 1613
Test Item Value Level
IEC 61000-4-2 ESD Contact Discharge Air Discharge Contact Discharge Air Discharge 4

4

IEC 61000-4-3 RS Enclosure Port Enclosure Port 3
IEC 61000-4-4 EFT AC Power Port DC Power Port Signal Port AC Power Port DC Power Port Signal Port 4

4

4

IEC 61000-4-5 Surge AC Power Port AC Power Port DC Power Port DC Power Port Signal Port AC Power Port AC Power Port DC Power Port DC Power Port Signal Port 4

4

4

3

4

IEC 61000-4-6 CS 0.15-80MHz 0.15-80MHz 3
IEC 61000-4-8 PFMF (Enclosure) (Enclosure) 5
IEC 61000-4-11 DIP  

AC Power Port

 

AC Power Port

 

IEC 61000-4-12 Damped Oscillatory AC Power Port AC Power Port 3
Shock Drop Vibration MIL-STD-810G Method 516.5

MIL-STD-810F Method 516.5

MIL-STD-810F Method 514.5 C-1 & C-2

RoHS2 Yes
MTBF TBD
Warranty 5 years
Model Technology Ethernet G.Ethernet/SFP GNSS Module Sync Module Power Modules
XTS8610 GPS 2 2 Single Band N/A Support Two Hot Swappable

Power Modules.

2x NTS8610-AC or

2x NTS8610-DC or

1x NTS8610-DC +

1x NTS8610-AC

XTS8610M GPS 2 2 Multi-Bands N/A
XTS8610-S2 GPS 2 2 Single Band S2
XTS8610M-S2 GPS 2 2 Multi-Bands S2
XTS8610-S3 GPS 2 2 Single Band S3
XTS8610M-S3 GPS 2 2  

Multi-Bands

S3

 

Power Modules
XTS8610-DC Rated Supply Voltage: ±24 – ±60 VDC

Input Voltage Range: ±20 – ±66 VDC

XTS8610-AC Rated Supply Voltage:

110 – 240 VAC, 50/60 Hz

110 – 250 VDC

Input Voltage Range:

85 – 264 VAC, 50/60 Hz

88 – 300 VDC